Sew 2120 ER
|
FEATURES
● Capable of measuring earth resistance and earth voltage.● 2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.● The leads are supplied as standard accessories for simplified two-wire measuring system.● 0Ω adjustment. ● Battery operated.● Data hold function.● Low battery indication.● Calibration performed with supplied test leads.
SPECIFICATIONS
Measuring ranges
Earth resistance 0-20Ω / 0-200Ω / 0-2000Ω Earth voltage 0-200 Vac(40-500Hz)
Accuracy
Earth resistance ±(2%rdg+2dgt) or ±0.1Ω, which is greater Earth voltage ±(1%rdg+2dgt)
Earth resistance resolution
0-20Ω : 0.01Ω 0-200Ω : 0.1Ω 0-2000Ω : 1Ω
Measuring system
Earth Resistance by constant current inverter 820Hz approx. 2mA
Display
3½ digit (2000 counts)
0Ω adjustment
ˇ
Open circuit indication
LED will be unlit
Low battery indication
“ “symbol... |
3 Wire (Digital) Earth Resistance Testers
|
|
|
|
Sew 1820 ER
|
FEATURES
● Capable of measuring earth resistance and earth voltage.● 2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.● The leads are supplied as standard accessories for simplified two-wire measuring system.● Battery operated.● Data hold function.● Low battery indication.● Calibration performed with supplied test leads.
SPECIFICATIONS
Measuring ranges
Earth resistance 0-20Ω / 0-200Ω / 0-2000Ω Earth voltage 0-200 Vac(40-500Hz)
Accuracy
Earth resistance ±(2%rdg+2dgt) or ±0.1Ω, which is greater Earth voltage ±(1%rdg+2dgt)
Earth resistance resolution
0-20Ω : 0.01Ω 0-200Ω : 0.1Ω 0-2000Ω : 1Ω
Measuring system
Earth Resistance by constant current inverter 820Hz approx. 2mA
Display
3½ digit (2000 counts)
Open circuit indication
LED will be unlit
Low battery indication
“ “symbol appears on the display
Data hold indication
... |
3 Wire (Digital) Earth Resistance Testers
|
|
|
|
Sew 1120 ER
|
FEATURES
● Capable of measuring earth resistance and earth voltage.● 2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.● The leads are supplied as standard accessories for simplified two-wire measuring system.● 0Ω adjustment. ● Battery operated.● Data hold function.● Low battery indication.● Calibration performed with supplied test leads.
SPECIFICATIONS
Measuring ranges
Earth resistance 0-20Ω / 0-200Ω / 0-2000Ω Earth voltage 0-200 Vac(40-500Hz)
Accuracy
Earth resistance ±(2%rdg+2dgt) or ±0.1Ω, which is greater Earth voltage ±(1%rdg+2dgt)
Earth resistance resolution
0-20Ω : 0.01Ω 0-200Ω : 0.1Ω 0-2000Ω : 1Ω
Measuring system
Earth Resistance by constant current inverter 820Hz approx. 2mA
Display
3½ digit (2000 counts)
0Ω adjustment
ˇ
Open circuit indication
LED will be unlit
Low battery indication
“ “symbol appears on the display
Data hold... |
3 Wire (Digital) Earth Resistance Testers
|
|
|
|
Sew ST-1520
|
● Capable of measuring earth resistance and earth voltage.● 2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.● Auto power off function.● The timer operates automatically for about three to five minutes when the "PUSH BUTTON SWITCH" and "TIMER ON BUTTON" are pressed together. This will keep test "ON" for the duration of the timer.● Timer for test function (count 3-5 minutes).● Battery operated.● Data hold function.● Small and light weight.● Calibration performed with supplied test leads.
SPECIFICATIONS
Measuring ranges
Earth resistance 0-20Ω / 0-200Ω / 0-2000Ω Earth voltage 0-200 Vac (40-500Hz)
Accuracy
Earth resistance ±(2%rdg+2dgt) or ±0.1Ω, which is greater Earth voltage ±(1%rdg+2dgt)
Earth resistanceresolution
0-20Ω : 0.01Ω 0-200Ω : 0.1Ω 0-2000Ω : 1Ω
Measuring system
Earth Resistance by constant current inverter 820Hz approx. 2mA.
... |
3 Wire (Digital) Earth Resistance Testers
|
|
|
|
Sew 1620 ER
|
● Microprocesser-controlled. ● Measures earth resistance in three ranges : 40Ω, 400Ω, 4kΩ.● Capable of measuring earth voltage.● 3 ¾ digit (4000 counts).● LCD backlight display.● 2mA measuring current permits the testing of earth resistance without tripping earth leakage current breakers in the circuit under test.● Data hold function.● Relative function.● Auto power-off function.● Low battery indication.● Calibration performed with supplied test leads.
SPECIFICATIONS
Measuring ranges
Earth Resistance 0~40Ω / 0~400Ω / 0~4kΩ Earth Voltage 0~400V (40~500Hz)
Accuracy
Earth Resistance ±(2%rdg+3dgt) Earth Voltage ±(2%rdg+3dgt)
Earth resistanceresolution
0~40Ω : 0.01Ω 0~400Ω : 0.1Ω 0~4kΩ : 1Ω
Measuring system
Earth resistance by constant current inverter 820 Hz, 2mA approx.
Dimensions
163(L) x 102(W) x 50(D)mm
Weight (battery included)
Approx. 440g
Power source
1.5V (AA) x 6
Safety standards
EN 61010-1 CAT IV 400V EN 61326-1 EN 61557-1 EN 61557-5
|
3 Wire (Digital) Earth Resistance Testers
|
|
|
|
Sew 6201 IN (Ranges: 5kV, 10kV)
|
FEATURES
● Microprocessor-controlled.● High quality Taut Band movement.● Two insulation test voltages.● Insulation resistance, auto ranging on all ranges.● Low Battery LED indication.● Beeper warning of external voltage.● Fully protected : crow bar.● Housed in carry case.
SPECIFICATIONS
Test voltage (DC V)
5000V
10000V
Measuring ranges
0-200GΩ
0-400GΩ
Accuracy
±5% of full scale
Live warning
>500V AC
Operating-temperature
0°C to 40°C
Operating-humidity
85% Max. relative humidity
Dimensions
330(L) × 260(W) × 160(D) mm
Weight (battery included)
Approx. 3500g
Power source
1.5V “C”× 8 Alkaline batteries
|
Analogue (1kV up) H.V. Insulation Testers
|
|
|
|
Sew 6200 IN (Ranges: 2.5kV, 5kV)
|
FEATURES
● Microprocessor-controlled.● High quality Taut Band movement.● Two insulation test voltages.● Insulation resistance, auto ranging on all ranges.● Low Battery LED indication.● Beeper warning of external voltage.● Fully protected : crow bar.● Housed in carry case.
SPECIFICATIONS
Test voltage (DC V)
2500V
5000V
Measuring ranges
0-100GΩ
0-200GΩ
Accuracy
±5% of full scale
Live warning
>500V AC
Operating-temperature
0°C to 40°C
Operating-humidity
85% Max. relative humidity
Dimensions
330(L) × 260(W) × 160(D) mm
Weight (battery included)
Approx. 3500g
Power source
1.5V “C”× 8 Alkaline batteries
|
Analogue (1kV up) H.V. Insulation Testers
|
|
|
|
Sew 6213A IN (Ranges: 0.5kV to 10kV 0.5kV increment steps)
|
FEATURES
● Microprocessor-controlled.● 2 ×16 characters; large intelligent LCD module.● 20 Insulation test voltages 500V, 1kV, 1.5kV, 2kV, 2.5kV, 3kV, 3.5kV, 4kV, 4.5kV, 5kV, 5.5kV, 6kV, 6.5kV, 7kV, 7.5kV, 8kV, 8.5kV, 9kV, 9.5kV, 10kV.● Ener-Save™ feature to extend battery life.● Bar-graph indicates test voltage; rise and decay can be observed.● Visual and audible warning if external voltage is present (>500Vac or Vdc.)● Insulation resistance; auto-ranging on all ranges.● Overload protection.● Low battery indicator (read time battery voltage measurement).● Measures insulation time duration of the test.● Low battery consumption.● Better than 10% accuracy on all ranges.● Auto-off.● Calculates Dielectric Absorption Ratio (DAR) automatically.● Calculates Polarization Index (PI) automatically.
SPECIFICATIONS
Test voltage
From 500Vdc to 10kVdc Adjustable in 500V steps
Preset buttons
1kV / 2.5kV / 5kV / 10kV
Measuring ranges
800kΩ-500GΩ (auto-ranging)
Accuracy
± 5% ± 2 digits
... |