Sew 1812 EL
|
FEATURES
● Microprocessor-controlled.● 2Lines × 16 Characters LCD.● Very low consumption.● Menu-driven.● Accurate digital readout of disconnection time.● Automatic data hold function.● Zero Crossing Circuitry permit testing at 0° or 180°.● Disconnection Phase Polarity shown on LCD display.● Auto-off and off override.● Polarity Trip indicator (Positive of Negative Phase).● Wiring polarity indicator.● Measure voltage and frequency between Line and Earth before testing.
SPECIFICATIONS
Current settings
3mA, 5mA, 7mA, 10mA, 15mA, 20mA, 30mA, 35mA, 50mA, 100mA, 125mA, 150mA, 175mA, 250mA, 300mA, 375mA, 500mA.
Current selection
Rotary switch selector
Phase start selection 0° and 180°
Referenced to Earth Yes
Over-temperature protection
Yes (3 sensors)
Wiring correctness indication
Yes (LEDs)
Trip indicator
Yes (LEDs)
Phase polarity trip Indicator
Yes (LCD) Referenced to Earth
Voltmeter (L-E)
20Vac ~ 280Vac
Timer resolution
1ms (Max. Time = 2.999s)
Timer... |
Digital ELCB Testers
|
|
|
|
Sew 1813 EL
|
FEATURES
● Microprocessor-controlled.● 2 Lines × 16 characters LCD.● Very low consumption.● Suitable for domestic version.● Better than 3% accuracy (current).● Menu-driven.● Accurate digital readout of disconnection time.● Accurate digital readout of disconnection sensitivity.● Automatic data hold function.● Zero crossing circuitry permit testing at 0° or 180°.● Disconnection phase polarity shown on LCD display.● Auto off and off override.● Polarity trip indicator (positive or negative phase)● Wiring polarity indicator.● Measure voltage between Line and Earth before testing.● 60Hz available.
SPECIFICATIONS
System voltage (50Hz / 60Hz)
550V 380V 240V
Current settings
2-999mA ac
Current selection
Knob
Phase start selection referenced to earth
0° and 180°
Over-temperature protection
Yes
Wiring correction indication
Yes
Phase polarity trip indicator
Yes
Operating voltage (L-E)
110 Vac to 317 Vac
Timer resolution
1ms (Max. Time=19.999s)
Timer accuracy
1ms ±1ms
... |
Digital ELCB Testers
|
|
|
|
Sew 2712 EL
|
FEATURES
● Microprocessor-controlled.● 2 Lines × 16 characters LCD.● Very low consumption.● 50Hz and 60Hz operation.● Menu-driven.● Accurate digital readout of disconnection time.● Automatic data hold function.● Over temperature protection.● Over voltage protection.● Fuse protection.● Zero crossing circuitry permit testing at 0° or 180°.● Disconnection phase polarity shown on LCD display.● Auto off and off override.● Polarity trip indicator (positive or negative phase)● Wiring polarity indicator.● Measure voltage between Line and Earth before testing.● Frequency measurement indication.
SPECIFICATIONS
Operating voltage (L-E) (50Hz or 60 Hz)
Version A : 240 Vac Version B : 230 Vac Version C : 220 Vac Version D : 110 Vac
Current settings
3mA, 5mA, 10mA, 15mA, 20mA, 30mA, 50mA, 100mA, 150mA, 250mA, 300mA, 500mA.
Current selection
Rotary switch selector
Phase angle setting
0° and 180° selectable
Wiring correctness indication
Yes (LEDs)
Trip indicator
Yes (LCD)
Phase polarity trip indicator
Yes... |
Digital ELCB Testers
|
|
|
|
Sew 2820 EL
|
FEATURES
● Microprocessor-controlled.● Operating voltage 100-450V L-E.● Rated current 999mA, at 317V AC/50Hz.● Checks ELCB trip time and trip point (sensitivity).● Auto off and auto ranging.● Phase angle selection(0° / 180°).● Indicates tripping phase angle.● Impact resistant enclosure.● Over temperature shut-down.● Transient protection.● Suitable for heavy industrial use.● Fused.
SPECIFICATIONS
Trip current-range
0-1A at 317V (Auto-Rang Programmable)
Trip current- resolution
1mA
Operating voltage (L-E)
100 - 450V
Phase angle setting
0° and 180° selectable
Timer-max
99.999s
Timer resolution
1ms
Typical Accuracy
Trip-current
±1%rdg±1mA
Trip-time
±1%rdg±1dgt
Voltage
±3%rdg±1dgt
Operating temperature - humidity
-10°C to +40°C 80% Max. relative humidity
Dimensions
170(L) × 120(W) × 95(D)mm
Weight (battery included)
Approx. 800g
Power source
1.5 (AA) × 8
Safety standard
EN 61010-1 CAT III 450V EN... |
Digital ELCB Testers
|
|
|
|
Sew 4112 EL
|
FEATURES
● Microprocessor-controlled.● 2 Lines × 16 Characters LCD.● Very low consumption.● Menu-driven.● Accurate digital readout of disconnection time.● Automatic data hold function.● Zero Crossing Circuitry permit testing at 0° or 180°.● Disconnection Phase Polarity Shown on LCD.● Auto off and off override.● Polarity Trip indicator (Positive or Negative Phase).● Wiring polarity indicator.● Measure voltage between line and earth before testing.● Indicates frequency of voltage L-E.
SPECIFICATIONS
Current settings
3mA, 5mA, 7mA, 10mA, 15mA, 20mA, 30mA, 35mA, 50mA, 100mA, 125mA, 150mA, 175mA, 250mA, 300mA, 375mA, 500mA.
Current selection
Rotary switch
Phase start selection 0° and 180°
Referenced to Earth Yes
Over-temperature protection
Yes
Wiring correctness indication
Yes
Trip indicator
Yes
Phase polarity trip Indicator
Yes
Operating voltage (L-E)
Referenced to Earth 240Vac-50Hz or 60Hz Voltage Model (Vac)
Timer resolution
1ms (Max. Time=19.99s)
Timer accuracy
1ms... |
Digital ELCB Testers
|
|
|
|
Sew 6220 EL
|
FEATURES
● Microprocessor technology ensures high
performance accuracy and reliability.● Fully programmable via tactile key pad.● Direct readout of disconnection, time or current.
● Voltage measured during test.● Housed in a heavy duty carry case.● Suitable for all industrial, mining and domestic
environments.● Display can be customized for special orders.● Indicate voltage and trip Current/Time.● Use binary principle.● True resistor switching.
SPECIFICATIONS
Rated tripping current at 317V
1000mA (2000mA on special orders)
Lowest resolution
1mA
System voltage
230 / 380 / 550V (50Hz)
Maximum trip time
99.99s
Highest resolution
10ms
Typical Accuracy
Rated trip current
±1%rdg ± 2dgt
Voltage range
±1%rdg ± 1dgt
Trip-time
±1%rdg ± 2dgt
Voltage
0°C to 40°C
Operating-humidity
80% Max. relative humidity
Dimensions
330(L) × 260(W) × 160(D)mm
Weight (battery included)
Approx. 3700g
Power source
1.5V “C” × 8... |
Digital ELCB Testers
|
|
|
|
Sew 6221 EL
|
FEATURES
● Microprocessor-controlled.● Indicates phase rotation.● Indicates phase presence.● Tests for disconnection sensitivity.● Indicates battery status.● Tests for disconnection time.● Measures voltage phase to earth.● Select one of 3 Phase to test ELCB.● Color-coded test leads.● Phase presence indication from as low as 100Vac.● Very low consumption.● Fused earth leakage tester.● ELCB works 50Vac to 330Vac 50Hz / 60Hz.● Led indication of Voltage on ELCB.● Phase rotation and presence does not require battery to indicate.● EN 61010-1 CAT III 550V. EN 61326-1
SPECIFICATIONS
Determination of the Phase Presence
Nominal Voltage for Phase Presence Indication (the voltage required for the neon lamps L1, L2, L3 to lit up)
From 100Vac to 450Vac.
Frequency Range
From 10Hz to 400Hz.
Determination of the Phases Rotary Field Direction
Direction (the voltage required to have the direction LEDs L1-L2-L3 or L2-L1-L3 to indicates)
From 100 to 450Vac.
Frequency Range
From 2Hz to... |
Digital ELCB Testers
|
|
|
|
Sew DEL-101
|
FEATURES
● Mains wiring polarity check.● ELCB/RCD testing.● Measuring ear for line current.● Measuring ear for leakage current.● Helps calculate insulation resistance.● Helps calculate power consumption.● Helps fault finding of standing earth fault.● Fused main adapter.● Appliance testing (with the aid of a clamp meter).● Fused appliance socket.● No batteries required.● HRC fuse inside.● Fused, color-coded universal test sockets.● Universal mains IEC Lead.
SPECIFICATIONS
Voltage / power input
Universal IEC LEAD
240V/10A
Wiring polarity check
Nominal Voltage
240Vac
Frequency
50/60Hz
Mains Voltage Tolerance
±10%
Elcb / rcd tester
Nominal Voltage
240Vac
Frequency
50/60Hz
Current Tolerance (current proportional to Line to Earth Voltage)
±10%
Universal test sockets
Nominal Voltage
240Vac
Frequency
50/60Hz
Mains Voltage Tolerance
±10%
Fuse
10A
Appliance tester
Nominal... |